Master Programming Level

3.5.3 Output Circuits

The options for the Output Circuits on the control panel main circuit board can be configured by
pressing 2 while viewing Programming Screen #2. The following screens will be displayed:
PROGRAMMING
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
The Output Circuits can be configured independently by pressing 1 for Output 1, 2 for Output 2, 3
for Output 3 or 4 for Output 4.
To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
OUTPUT CIRCUITS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
NAC Selection Screen
OUTPUT CIRCUITS
1=OUTPUT 4
NAC Selection Screen
OUTPUT #
1=ENABLED
2=TYPE
RELEASE CIR 1
UNSUPV SHORTS
Output Screen #1
OUTPUT #
1=SILENCE
2=AUTO SILENCE
3=SIL INHIBIT
Output Screen #2
OUTPUT #
1=CODING
Output Screen #3
Programming
YES
N/A
N/A
NO
N/A