Network Connections; Ethernet Network; Lcn Network - Honeywell HP ProLiant DL360P Gen8 Service Manual

Table of Contents

Advertisement

Item
1
2
3
4
5
6
7
8
9
4.2

Network connections

NOTE
A Local Control Network Processor (LCNP) board and LCN Media Access Unit (MAU) are no
longer used if the Server has been upgraded to be an ELCN node.
Each Honeywell-configured platform must be connected to an ETHERNET network.

Ethernet network

l
LCN cables
l

LCN network

l
LCN connections
l
MAU connection
l
ControlNet Network
l
4.2.1
Ethernet network
ETHERNET 10/100/1000 Base T connection is the standard connection used on the Honeywell-
configured platform. An on-board dual NIC must be used for FTE configuration.
4.2.2
LCN network
The connection to the LCN is made through a Local Control Network Processor (LCNP4e/LCNp4e2)
card. The LCNP4e/LCNp4e2 card is a Honeywell PWA that allows the TPS Operator Station to emulate
Universal Stations. This card provides the communication path for the Operator Station to other LCN
modules. The LCNP4e/LCNp4e2 consists of an LCNP4e/LCNp4e2 Card, a MAU cable and the LCN
MAU (Media Access Unit). The LCNP4e/LCNp4e2 card is a PCIe card and is located in PCI-ex8 slot 1.
The LCNP4e/LCNp4e2, MAU and MAU cable are required on Server Platform. The LCN node address
Description
Slot 2 PCIe 3.0 x16 (full height/half length)
FlexibleLOM ports
Video connector
Serial connector
Slot 1 PCIe 3.0 x8 (low profile)
iLO management port
USB connectors (4)
Power supply bay 2
Power supply bay 1
- 36 -
Chapter 4 - Operation

Advertisement

Table of Contents