2: Nac (Notification Appliance Circuit); Enabled; Nac Coding - Honeywell NOTIFIER SFP-5UD Series Manual

Fire alarm control panels
Hide thumbs Also See for NOTIFIER SFP-5UD Series:
Table of Contents

Advertisement

Programming
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Description, Adjective
or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire field is replaced with the field entered for
the previous device programmed, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or
Noun field may now be changed letter-by-letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number
is incremented by one. If the last character is a letter, it changes to a 0. If the last character goes from 9 to 0 and the characters to the
left of the last character are also numbers, they are also incremented (overflow)
The above increment function may be repeated with each press of the zero key
As an example, the user could quickly enter 'FLR_3_ROOM_305' as follows:
1.
The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3.
2.
With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor
automatically jumps from the first to the last letter of the Noun field.
3.
With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305.
4.
Press the Enter key to store the information.
3.5.2 NAC (Notification Appliance Circuit)
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2 for NAC 2, 3 for NAC 3, or 4 for NAC
4.
To program an NAC circuit, press the number corresponding to the NAC to be programmed. The following screens will be displayed for
each selection:

Enabled

NAC #
1=ENABLED
2=CODING
STEADY
NAC Screen #1

NAC Coding

The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate
when activated. Pressing 2 while viewing NAC Screen #1 will cause the following displays to appear:
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
The programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding
selections are:
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
Two Stage 3 Minutes or 5 Minutes - refer to "Two Stage Operation" on page 65 for a description of this feature
Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to "Synchronized NAC Operation" on
page 65 for additional information
64
The options for the NACs on the control panel main circuit board can be configured by pressing 2 while
viewing Programming Screen #2. The following screens will be displayed:
1=NAC 1
2=NAC 2
NAC Selection Screen
NAC #
1=ENABLED
YES
2=CODING
STEADY
NAC Screen #1
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent
the selected main circuit board NAC from activating its devices. Each press of the 1 key will cause the dis-
play to toggle between Enabled Yes and Enabled No.
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is enabled.
CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2
NACS
3=NAC 3
4=NAC 4
NAC #
1=SILENCE
2=AUTO SILENCE
3=SIL INHIBITED
NAC Screen #2
CODING
1=SYNC SYSTEM SENSR
2=SYNC WHEELOCK
3=SYNC GENTEX
Coding Screen #3
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
Master Programming Level
YES
NO
NO
CODING
1=SYNC FARADAY
2=SYNC AMSECO
Coding Screen #4