Wire Requirements
D.2 SFP-5UDC & SFP-10UD(C/E) NAC Wiring
The following table lists NAC wiring requirements for the SFP-5UDC & SFP-10UD(C/E) FACP which utilizes the FLPS-7 power sup-
ply.
NAC Load
(Amps)
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2005 Edition)
Table 8, Conductor Properties.
NOTE: These distances reflect the worst case scenario and are based on the current draw of the highest candela strobes at the low end of
the supported NAC voltage with the entire load at the end of the circuit. Further distances can be achieved by performing a point to point
voltage calculation that more accurately reflects the specific devices used and how they are dispersed on the circuit.
126
Max.
allowable
Max. allowable wire pair length
total loop
resistance
AWG 12
AWG 14
(ohms)
solid
solid
6.00
1554
977
3.00
777
489
2.00
518
326
1.50
389
244
1.20
311
195
1.00
259
163
0.86
222
140
0.75
194
122
0.67
173
109
0.60
155
98
0.55
141
89
0.50
130
81
Table D.3 NAC Wiring Requirements for FACP with FLPS-7 Power Supply
CLASS-B
(feet)
AWG 16
AWG 18
solid
solid
613
386
307
193
204
129
153
97
123
77
102
64
88
55
77
48
68
43
61
39
56
35
51
32
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
SFP-5UDC & SFP-10UD(C/E) NAC Wiring
CLASS-A
Max. allowable wire pair length
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
777
489
307
389
244
153
259
163
102
194
122
77
155
98
61
130
81
51
111
70
44
97
61
38
86
54
34
78
49
31
71
44
28
65
41
26
AWG 18
solid
193
97
64
48
39
32
28
24
21
19
18
16