Master Programming Level
24 Hour Test Time
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR T TIME
Primary/Secondary Screen #1
Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour Test to the Central Station. A flashing
cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time (0000 =
midnight and 2359 = 11:59PM).
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed:
24 HOUR TEST TIME
ENTR USING 24HR TIME
RANGE 0000-2359
24 Hour Test Time Screen
Programming
81