The SFP-5UD is a five zone FACP (Fire Alarm Control Panel) and the SFP-10UD is a ten zone FACP. The information in this manual
refers to both the SFP-5UD and SFP-10UD unless otherwise specified. The combination control and digital communicator panels pro-
vide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compat-
ible with System Sensor's i
FACP indicating the need for cleaning and a supervisory 'freeze' signal when the ambient temperature falls below the detector rating of
o
approximately 45
with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper
switches and other normally-open contact devices. Refer to the Notifier Device Compatibility Document for a complete listing of com-
patible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm,
Trouble and Supervisory) and 24 VDC special application resettable and nonresettable power outputs. The FACP supervises all wiring,
AC voltage, battery level and telephone line integrity. Available accessories include local and remote upload/download software, remote
annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone net-
work. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public
switched telephone network. Local programming interrogation is also possible using the PS-Tools and the USB port on the FACP. Any
personal computer with Windows
Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data and current status.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling
devices, illuminate an indicating LED, display alarm information on the panel's LCD, sound the piezo sounder at the FACP, activate the
FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.
The following versions of the SFP-5UD and SFP-10UD are available:
FACP Version
SFP-5UD
SFP-5UDC
SFP-5UDE
SFP-10UD
SFP-10UDC
SFP-10UDE
NOTE: Unless otherwise specified, the information in this manual applies to all versions of the panels.
1.1 Product Features
•
Built-in DACT (Digital Alarm Communicator/Transmitter)
•
Style B (Class B) IDC (Initiating Device Circuit)
SFP-5UD - five programmable IDCs
SFP-10UD - ten programmable IDCs
•
Four Style Y (Class B) NAC (Notification Appliance Circuit) - special application power
•
Three programmable Form-C relays
•
Built-in Programmer
•
Touchtone/Rotary dialing
•
Programmable Make/Break Ratio
•
Optional Dress Panel: DP-51050B (black) or DP-51050 (red)
•
A modified Dress Panel is provided standard with Canadian models: includes an N-ANN-LED
Annunciator module
•
Optional Trim Ring TR-CE (red) or TR-CE-B (black) for semi-flush mounting the cabinet
•
ANN-BUS for connection to optional:
N-ANN-80 Remote LCD Annunciator
N-ANN-I/O LED Driver
N-ANN-S/PG Printer Module
N-ANN-RLY Relay Module
N-ANN-LED Annunciator Module
•
80-character LCD display (backlit)
•
Real-time clock/calendar with daylight savings time control
•
History log with 256 event storage
•
Control Buttons
ACK (Acknowledge)
12
Section 1: Product Description
3
detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the
F (refer to System Sensor i
Installation and Maintenance Instructions). In addition, the control panel is compatible
3
®
XP or newer, compatible modem with a speed of 2400 baud and PS-Tools may serve as a Service
Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps total 24 VDC output current
Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24 VDC output current.
Includes built-in N-ANN-LED Annunciator. This panel is approved for Canadian applications
Five Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24 VDC output current
Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24 VDC output current
Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24 VDC output current.
Includes built-in N-ANN-LED Annunciator. This panel is approved for Canadian applications.
Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24 VDC output current
Description