NFPA Standard-Specific Requirements
Notes:
1.
Reference the 411UD Manual for additional information
2.
Program the 411UD for slave operation
3.
The SFP-5UD/SFP-10UD must be programmed for AC Loss Reporting Delay This prevents the immediate transmission of a
trouble on the loss of AC power
4.
All connections between the control panel and the 411UD must be in conduit, less than 20 feet (610 cm) in length, in the same room
5.
Any zone of the 411UD can be wired to function as alarm, trouble or supervisory. In Figure B.1 on page 119, Channel 1/Zone 1 is
wired to the control panel's alarm relay, Channel 2/Zone 2 is wired to the control panel's trouble relay and Channel 3/Zone 3 is
wired to the control panel's supervisory relay
6.
Nonresettable 24 VDC power is supplied to the 411UD via TB9 terminals configured for nonresettable power on the FACP. Jumper
J4 on the 411UD must be removed for 24 VDC power
7.
End-of-Line resistors must terminate all 411UD circuits, including unused circuits
8.
A -VDC from the 411UD Trouble Contacts will activate the Trouble Input J6 on the FACP
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or
trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from
control panel to Municipal Box.
2.
Cut JP30 on the SFP-5UD/SFP-10UD main circuit board
to supervise placement of 4XTM module and circuit.
3.
Cut JP24 on the SFP-5UD/SFP-10UD main circuit board
to enable FACP Supervisory relay.
4.
Refer to "4XTM Transmitter Module Installation" on
page 33 for detailed information.
120
Polarities shown in alarm condition
Figure B.2 Municipal Box Connected to 4XTM Transmitter Module
Municipal Box Circuit
Nonpower-limited
-
+
4XTM
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
FIRE
+
-
Gamewell Model M34-56
Local Energy Municipal
Box