Program with °F temperature-converted value and highest/lowest process alarm
(I/O slot fixed-points assigned: based on changeable type)
Details of initial setting
1.
Used channel: CH0
2.
Sensor type: Pt100
3.
Temperature unit: °F
4.
High/low process alarm setting: High = 2170, Low = 2070
Description of program
1.
If P00000 is ON, the temperature-converted value of CH0 is output to D0.
2.
The output contact is installed on the slot number 2. This program is used to trigger
output (alarm) by means of the highest/lowest process function if the highest/lowest
process alarm range is exceeded.
Program
Program example post I/O parameters setting
R200
Resistance Temperature Detector 2MLF-RD4A User's Guide
September 2010
Figure 80 – System configuration
Honeywell
6. Programming
6.3. Application program
123