Iec 61850 Actual Values - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 6: COMMUNICATIONS
NOTE:

IEC 61850 actual values

Remote device status values
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Buffered Reports OptFlds
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the option fields. The following bits are
Plus
supported by the D90
Bit 1: sequence-number.
Bit 2: report-time-stamp.
Bit 3: reason-for-inclusion.
Bit 4: data-set-name.
Bit 5: data-reference.
Bit 6: buffer-overflow.
Bit 7: entryID.
Bit 8: conf-revision.
Buffered Reports TrgOps
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the trigger options. The following bits are
Plus
supported by the D90
Bit 1: data-change.
Bit 4: integrity.
Bit 5: general interrogation.
Buffered Reports IntgPd
Range: 0, or 250 to 4294967295 in steps of 1
Default: 0
This setting specifies the integrity period for buffered reports.
Please disconnect any IEC 61850 client connection to the D90
changes to the buffered report configuration. Disconnecting the rear Ethernet connection
Plus
from the D90
will disconnect the IEC 61850 client connection.
Actual values for IEC 61850 are available in two locations. A general IEC 61850
communications actual value is available through the Actual Values > Communications >
Communication menu. The IEC 61850 GOOSE input and output actual values are available
through the Actual Values > Communications > Inputs/Outputs menu.
Select the Actual Values > Communications > Inputs/Outputs > Remote Devices Status
menu item to open the remote device status values window.
.
.
IEC 61850 COMMUNICATIONS
Plus
prior to making setting
137