FRONT PANEL OVERVIEW
76
Figure 54: Typical annunciator display
There are three control buttons at the bottom of the display.
The Next Page button navigates through the configured alarm, self-test and product
information pages. It should be noted that pages that contain no configured alarms
are not displayed.
The Next Alarm button navigates horizontally though the current alarms that are
active, from left-to-right, starting with the first row of alarms. A border is drawn
around the current alarm.
The Ack/Reset button is used to acknowledge alarms or reset latched and
acknowledgeable alarms that are in the ringback state.
The annunciator alarm sequence conforms to ISA 18.1-1979 (R1992) standard, type R.
Figure 55: Annunciator alarm sequence
The annunciator states are described in the following table.
Table 5: Acknowledgeable alarm states
Sequence (initial
Process (status)
state)
Normal
Normal
Normal
Abnormal
Alarm
Normal
Alarm
Normal
Alarm
Abnormal
Acknowledged
Abnormal
Acknowledged
Normal
Ringback
Normal
Ringback
Abnormal
The visual indications are displayed as follows.
Off: grey text on a darker grey background.
On: user-configurable.
Fast flash: Alternating between the off state and the on state two times per second.
Pushbutton
(input)
N/A
N/A
N/A
Acknowledged
Acknowledged
N/A
N/A
Reset
N/A
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
Sequence (final
Visual indication
state)
N/A
Off
Alarm
Fast flash
Alarm
Fast flash
Normal
Off
Acknowledged
On
Acknowledged
On
Ringback
Slow flash
Normal
Off
Acknowledged
On