GE D90 Plus Instruction Manual page 598

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

SELF-TESTS
588
CH 1 DIRECT DEVICE OFF, CH 2 DIRECT DEVICE OFF
Description: A direct device is specified in the configuration but is not connected to the
network. This self-test should occur within 2 seconds of disconnecting the device.
Severity: Protection is available. Direct input/output messaging with the offline device is
not available.
If this message appears, check that all devices that are connected to the direct input/
output network are properly configured. Check the direct input/output wiring.
CH 1 DIRECT RING BREAK, CH 2 DIRECT RING BREAK
Description: The direct input/output settings are configured for a ring, but the connection
is not in a ring. This self-test is asserted approximately 2 seconds after a disconnection
occurs in a ring configuration.
Severity: Protection and direct input/output messaging is available. However, there is no
redundant path available.
If this message appears, check the direct input/output configuration and wiring.
COMMUNICATION CARD TROUBLE
Description: An error has been encountered on the communications module.
Severity: Protection is available.
If this message appears, update the order code to clear the self-test error.
COMM HIGH TRAFFIC
Plus
Description: The D90
Severity: Protection is available.
This message indicates that the D90
more Ethernet ports through the network filtering settings.
CPU CARD TROUBLE
Description: There may be a problem with the CPU card.
Severity: Protection is available.
If this message appears, cycle the control power If the alarm recurs, contact GE Grid
Solutions.
DELAYED AUTOMATION EXECUTION
Description: Execution of the automation logic is longer than specified.
Severity: Protection is available. Automation logic may not produce expected results.
If this message appears, review the automation logic to confirm correct programming.
Move less critical tasks to an automation block with a slower scan.
ETHERNET PORT 1 FAILURE, ETHERNET PORT 2 FAILURE, ETHERNET PORT 3 FAILURE
Description: The indicated Ethernet port is not connected to a LAN.
Severity: Protection is available. Remote communications may not be available.
If this message appears, ensure that the external Ethernet switch is operational and
properly configured. Check for a link light at both ends of the Ethernet cable. If there is
no link light, replace the Ethernet cable. If these steps do not solve the problem, replace
the communications module.
FILE SYSTEM TROUBLE
Description: System files are missing on the flash disk during the boot process or files are
deleted or modified after the system was booted.
Severity: Protection is available.
If this message appears, repeat the firmware upgrade process.
FRONT PANEL MISMATCH
Description: The order code does not match the front panel type.
Severity: Protection is available.
If this message appears, update the order code to clear the self-test error.
is actively limiting IP bandwidth usage.
Plus
is actively limiting bandwidth usage in one or
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 14: TESTING

Advertisement

Table of Contents
loading

Table of Contents