CHAPTER 15: THEORY OF OPERATION
NOTE:

Pilot scheme and phase selector coordination

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
used). The permissive echo is programmed as a one-shot logic. The echo is sent only once
and then the echo logic locks out for a user-specified period. The duration of the echo
pulse does not depend on the duration or shape of the received RX signal but is
programmable with the
Echo Duration
overreaching protection elements operates.
In single-pole tripping, single-bit channel applications the signal received on bit 1 (RX1) is
echoed back on bit 1 (TX1). In two-bit and four-bit applications, the following echo tables
apply for operands and transit codes.
Table 46: Echo table for two-bit channels
Local determination of fault type
AG
BG
CG
AB, ABG, BC, BCG, CA, CAG, 3P, or unrecognized
Table 47: Echo table for four-bit channels
Local determination of fault type
AG
BG
CG
AB, ABG, BC, BCG, CA, CAG, 3P, or unrecognized
For the directional comparison unblocking scheme, the echo is performed in the same
manner as the hybrid POTT echo, but by additionally applying the following logic for both
the Rx (received) and LOG (loss-of-guard) for each channel: ECHO = LOG AND Rx.
The pilot schemes use the phase selector for local fault type identification. The latter may
fail to respond to certain fault scenarios. Examples include simultaneous forward and
reverse fault, simultaneous SLG and LL fault involving different phases (for example, AG
and BC) or two simultaneous faults in the same direction but at very different locations.
The phase selector is optimized to either indicate correctly the forward fault or to assert
the VOID flag. For example, a combination of AG and BC is not a valid fault type. Rather, it is
two different simultaneous faults and as such cannot be described by any single fault
pattern. Therefore, the phase selector would assert the VOID flag.
The VOID phase selection combined with a local trip request (such as high-set directional
overcurrent) will result in three-pole trip as per the trip output logic.
The pilot schemes, however, try to recover additional information from the distance
elements. Each scheme uses a forward-looking (either underreaching or overreaching)
distance zone. A given pilot scheme analyzes this zone for fault type identification if the
phase selector asserts its VOID flag. The DUTT scheme uses zone 1, while all other schemes
use zone 2. The schemes analyze all six fault loops of the zone to determine the fault type.
For example, simultaneous forward AG and reverse BG faults may result in the VOID
indication. The POTT scheme would analyze the zone 2 response. As only the AG element is
picked up, the local phase selection is determined as AG. This is a correct indication.
Depending on the number of bits used for communications, the accuracy of the overall
response will be further improved as illustrated in the next section.
setting. The echo is sent back only if none of the
Echoed bits
TX1
1
0
1
sent back as received
Echoed bits
TX1
TX2
1
0
0
1
0
0
sent back as received
SINGLE-POLE TRIPPING
TX2
0
1
1
TX3
TX4
0
0
0
0
1
0
633