GE D90 Plus Instruction Manual page 621

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 15: THEORY OF OPERATION
NOTE:
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 541: Applications of the phase distance transformer settings
In the following tables, the suffix "_21P" indicates current or voltage inputs to the phase
distance (ANSI 21P) element.
Table 24: Phase distance input signals for delta-wye transformers
Transformer
Loop
connection
None
AB
BC
CA
Dy1
AB
BC
CA
Dy3
AB
BC
CA
PHASE DISTANCE APPLIED TO POWER TRANSFORMERS
Current transformation
I
=
I
-
I
_21P
AB
A
B
I
=
I
-
I
_21P
AB
A
B
I
=
I
-
I
_21P
CA
C
A
I
_21P =
I
3
A
A
I
_21P =
I
3
B
B
I
_21P =
I
3
C
C
I
_21P -
=
I
3
AB
C
I
_21P -
=
I
3
BC
A
I
_21P -
=
I
3
CA
B
Voltage transformation
V
=
V
_21P
AB
AB
V
=
V
_21P
BC
BC
V
=
V
_21P
CA
CA
1
(
)
V
=
V
-
V
_21P
AB
AB
CA
3
1
(
)
V
=
V
-
V
_21P
BC
BC
AB
3
1
(
)
V
=
V
-
V
_21P
CA
CA
BC
3
1
(
)
V
=
V
-
V
_21P
AB
BC
CA
3
1
V
=
(
V
-
V
)
_21P
BC
CA
AB
3
1
(
)
V
=
V
-
V
_21P
CA
AB
BC
3
611