CHAPTER 6: COMMUNICATIONS
Remote double-point status inputs
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of remote input events in the sequence of
events recorder.
Remote double-point status inputs are extracted from GOOSE messages originating in the
Plus
remote device. The D90
double-point status input must be programmed to replicate the logic state of a specific
signal from a specific remote device for local use.
The configurable GOOSE dataset items must be changed to accept a double-point status
item from a GOOSE dataset. Dataset items configured to receive any of
"GGIO3.ST.IndPos1.stV" to "GGIO3.ST.IndPos16.stV" will accept double-point status
information that will be decoded by the remote double-point status inputs configured to
this dataset item.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Inputs/Outputs > Remote DPS Inputs menu item to open the remote double-point status
inputs configuration window.
Figure 97: Remote double-point status inputs configuration settings
The following settings are available for each of the 16 remote double-point status inputs.
Name
Range: up to 12 alphanumeric characters
Default: RemDPS Ip 1
This setting specifies specific an exact identification (ID) for each remote double-point
status input.
Device
Range: Remote Device 1 through Remote Device 32
Default: Remote Device 1
This setting selects a remote device ID to indicate the origin of a GOOSE message.
provides 16 remote double-point status inputs. Each remote
IEC 61850 COMMUNICATIONS