CHAPTER 8: AUTOMATION

Selector switch

Selector switch operation
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
The selector switch element is intended to replace a mechanical selector switch. Typical
applications include setting group control or control of multiple logic sub-circuits in user-
programmable logic.
The selector switch provides for two control inputs. The step-up control allows stepping
through selector position one step at a time with each pulse of the control input, such as a
user-programmable pushbutton. The three-bit control input allows setting the selector to
the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected
position gets applied either after time-out or upon acknowledgement via separate inputs
(user setting). The selector position is stored in non-volatile memory. Upon power-up, either
the previous position is restored or the relay synchronizes to the current three-bit word
(user setting). Basic alarm functionality alerts the user under abnormal conditions; for
example, the three-bit control input being out of range.
The following figures illustrate the operation of the selector switch. In these diagrams, "T"
represents a time-out setting.
AUTOMATION CONTROL