ECP Status Codes

When the 7847i/7847i-E is configured for ECP mode, it sends status messages to the control
panels (e.g., VISTA-10P, VISTA-15P and VISTA-20P Series), for tamper, and network
connectivity failures. Some of the control panels display these on the keypad as "LngRng
Radio" followed by a 4-digit code (listed in table 4). In addition, the Contact ID codes (listed
in Appendix B) for these conditions are sent to the central station by the module.
STATUS CODE
0000
0880
0005
000F
0019
0400
0C80
0C8F

Alternative Modes (Zone Trigger, 4204 and Two-4204)

Zone Trigger Mode

There are six input zones available on the 7847i/7847i-E. Zones 1 and 2 are located on TB1
pin 5 and are selectable for +V, -V, or EOLR modes, which can detect both pulsed and steady
signals. The pulsed signal is reported as an alarm on zone 1 (Fire); the steady signal is
reported as an alarm on zone 2 (Burg). The implied pulse count for zone 1 is fixed to 3
pulses. The unit can be programmed to detect a single pulse on the input, characteristic of a
Panic indication on the Lynx Control Panel. If the programming option "Lynx Panic" is
enabled, the unit reports an alarm on zone 3 when it detects this single pulse. No restores
are reported for this zone.
Zones 3, 4, 5, 6 and 7 are voltage trigger inputs located on TB1 pins 6-10. If the Lynx Panic
feature is being used, do not connect zone 3.

4204 Emulation Mode

In the 4204 Emulation Mode, the 7847i/7847i-E communicates with a compatible Honeywell
VISTA series or First Alert control panel as though it were a 4204 Relay Module. If the Two
4204 Mode is enabled in the module, it acts as two 4204s at consecutive device addresses.
The control panel must be configured to recognize one or two 4204 relay modules accordingly.
On VISTA-32FB (or higher) control panels and First Alert equivalents, addresses 6 and 13
should not be used when the secondary 4204 is enabled. Messages are sent in Honeywell
High-Speed format.
NOTE: See your control panel Installation and Setup Guide for the number of 4204 modules supported.
The LynxR-I does not support 4204 mode.

4204 Emulation Mode Options

For control panels that do not support ECP communication, the 4204 Emulation modes
provide a means of sending up to eight unique reports based on defined system conditions. In
4204 mode, the 7847i/7847i-E functions as a logical 4204 Relay Module, where each relay
number, referred in the module as zone number, can be programmed to send a report based
on the output function programmed in the control for that relay. Each relay-zone can also be
programmed to send a restore message of the reported condition, can be set to delay
Table 4. Common ECP Keypad Displays Status Codes
Control panel lost communication
7847i/7847i-E
tamper
7847i/7847i-E has lost Ethernet connectivity.
7847i/7847i-E is not registered; account not activated.
7847i/7847i-E shutdown.
7847i/7847i-E
power
with 7847i/7847i-E.
7847i/7847i-E
power
7847i/7847i-E
power
Section 3: Programming the 7847i/7847i-E
DESCRIPTION
with 7847i/
detected (cover removed).
on reset AND the control panel lost communications
on reset AND tamper detected.
on reset AND tamper detected AND not registered.
7847i-E.
3-9