Honeywell AlarmNet 7847i-E Installation And Setup Manual page 19

Internet/intranet communication modules with remote services
Hide thumbs Also See for AlarmNet 7847i-E:
Table of Contents

Advertisement

PROMPTS
Second CS Port:
17
(80)
IP2 Supervision
18
30 Day_
Installation Key:
19
**********_
Verify Inst. Key:
20
**********_
Important Information Regarding Primary and Secondary Accounts (Questions 21-27)
Account information is provided by the central station administrator. If the control supports secondary
account reporting, you will need secondary account information, unless using a Private LAN (7847i-E). The
City ID, CS ID or Subscriber ID of the secondary account must differ from that of the primary account. If
Private LAN (7847i-E) is enabled, Prompts 24-27 will not be displayed.
Primary City ID
21
(??)_
Primary CS ID
22
(??)
Primary Sub ID
23
(????)
nd
En. 2
CS Y/N
24
(N)_
nd
2
City ID
25
(??)_
nd
2
CS ID
26
(??)_
nd
2
Sub ID
27
(????)_
Device Address
28
(03)_
ENTRY
OPTIONS
[80]
• 30 Day
• Daily
• Full Rate
• None
[0-9]
[0-9]
[01-99]
[01-FE]
[0001-9999]
[Y], [N]
[01-99]
[01-FE]
[0001-9999]
[01-30]
Section 3: Programming the 7847i/7847i-E
DESCRIPTION
Enter the Central Station Port Number.
NOTE: The CS Port number must match the "Listening
Port" question of the 7810iR-ent.
Sets the supervision timing for the secondary internet
receiver to send a test alarm if set to Daily or 30 Day,
or to send a status message to the 7810iR-ent if the
interval is set to Full Rate. Selecting Full Rate means
secondary supervision will be the same as primary.
NOTE: The second 7810iR-ent must be programmed to
supervise subscribers in order to generate a
communication failure.
Press the [space] key to scroll through the choices.
Enter the 10-digit Installation Key necessary for
communication with 7810iR-ent. If the key entry is
invalid, the prompt is repeated. See the Installation
Key paragraph in Section 1 for more information.
Re-enter the 10-digit Installation Key to verify key.
If verification fails, "Verify NOT OK" will be displayed
for one second and the display will return to the entry
of the installation key.
Enter the 2-digit primary city ID, 01-99 (decimal).
Enter the 2-digit primary central station ID number,
01-FE (HEX).
Enter the 4-digit subscriber account number for the
primary central station, 0001-9999 (decimal).
Applicable only if control supports Central Station #1
and #2 Category Enable reporting for the LRR device
(e.g., VISTA-128BP, FA1660C, etc.).
Used if reporting to a second central station is desired.
Press [N], go to Prompt 28: "Device Address."
Enter the 2-digit secondary city ID, 01-99 (decimal).
Enter the 2-digit second central station's ID number,
01-FE (HEX).
Enter the 4-digit subscriber account number for the
second central station, 0001-9999.
7847i-E
In ECP mode, the 7847i/
the panel as a Long Range Radio (LRR) device. Enter
the appropriate ECP device address. For VISTA-10 and
VISTA-20 series control panels, use address 03. For
other controls, see the control panel's Installation and
Setup Guide.
NOTES:
1. When programming the control, enable the LRR
output.
2. The device address must be unique from the "Keypad
Address" entered in Prompt 31, and the Multi-Mode
Address entered in Prompt 11.