2: Speaker Circuits - Honeywell ECC-50/100 Instruction Manual

Emergency command center, multipurpose emergency voice evacuation panels
Table of Contents

Advertisement

Output Circuits
2.6.2 Speaker Circuits
One Speaker Circuit Style Y (Class B) or Style Z (Class A) standard
Two Speaker Circuits Style Y (Class B) or Style Z (Class A) with ECC-50-25/70V
Four Speaker Circuits Style Z (Class B) or Style Z (Class A) or Style Y with ECC-CE6
Eight Speaker Circuits Style Z (Class B) or Style Z (Class A) or Style Y with ECC-50W-
25/70V and ECC-CE6
The integral amplifier and optional amplifier each provide audio for one Speaker Circuit. The cir-
cuit can be wired Style Y (Class B) or Style Z (Class A). Each supervised and power-limited
(Class 2) circuit is capable of 50 watts of power. Refer to the Fire•Lite Device Compatibility Docu-
ment for a listing of compatible speakers.
CAUTION:
!
MATCH PROPER POLARITY CONNECTIONS TO FIELD WIRING AND SPEAKERS. POLARITY
SHOWN IS IN THE STANDBY AND ALARM CONDITIONS.
ELR required for
Style Y - Class B only
15K, 1 watt, P/N:ELR-15K
Shielded cable is not required, however, shielded cable will reduce RFI/EMI emissions and suscep-
tibility. For additional information, refer to "Wiring Requirements" on page 101.
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
OBSERVE POLARITY
Style Z (Class A) Circuit
Shield
TB20
Figure 2.15 Speaker Circuit Connections
TB21
Installation