Honeywell ECC-50/100 Instruction Manual page 8

Emergency command center, multipurpose emergency voice evacuation panels
Table of Contents

Advertisement

This control panel has been designed to comply with standards set forth by the following regulatory agencies:
Underwriters Laboratories/Underwriters Laboratories Canada
National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code
Note: Audible signal appliances used in public mode applications, are required to have
minimum sound levels of 75 dBA at 10 feet (3 meters) and a maximum level of 120 dBA at the
minimum hearing distance from the audible appliance.
To ensure that the appliance is clearly heard, the audible appliance sound level must be at least
15 dBA above the average ambient sound level or 5 dBA above the maximum sound level with
a duration of at least 60 seconds, depending on which level is greater, with the sound level
being measured 5 feet (1.5 meters) above the floor.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 464 Audible Signaling Appliances
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1480 Speakers for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1711 Amplifiers for Fire Protective Signaling Systems
UL 1971 Signaling Devices for Hearing Impaired
UL 2572 Communication and Control Units for Mass Notification Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-11 Standard for Control Units for Fire Alarm Systems
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part 1
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents:
Fire•Lite Device Compatibility Document
ECC Distributed Audio Manual
ECC-FFT Manual
ECC-LOC Installation Document
ECC-RPU Installation Document
ECC-RM Installation Document
ECC-CE6 Installation Document
ECC-CE4 Installation Document
ECC-50W-25/70V Installation Document
ECC-XRM-70V Installation Document
MS-9200UDLS Series Manual
MS-9600(UD)LS Technical Manual
8
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
Document #15384
Document #LS10027-000FL-E
Document #LS10031-000FL-E
Document #LS10028-000FL-E
Document #LS10030-000FL-E
Document #LS10029-000FL-E
Document #LS10033-000FL-E
Document #LS10002-000FL-E
Document #LS10035-000FL-E
Document #LS10032-000FL-E
Document #52750
Document #52646

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc-50/100e

Table of Contents