Addressing External Data Bus Devices

2.13.3 70.7 V
The 70.7 V
where 70.7 V
vised during standby, alarm and while background music is playing when transformer is installed.
The transformer comes pre-installed onto a bracket for mounting to the chassis. Installation onto
the chassis depends on what other option modules are installed. See the ECC-XRM-70V Installation
Document. Refer to the drawing below.
NOTE: For 70.7V
CAUTION:
!
BEFORE INSTALLING ANY MODULES, MAKE CERTAIN ALL POWER (AC AND DC) HAS BEEN
REMOVED.
When installing the ECC-XRM-70V, be sure to:
carefully remove the factory-installed jumper plug from connector J12 on the main control
board.
set SW5 on the ECC-50/100 main control board to 70V operation.
2.14 Addressing External Data Bus Devices
The table below defines an address map for the external data bus devices which include the
ECC-LOC, ECC-RPU, ECC-RM, ECC-50DA, and ECC-125DA. Dipswitches are used on each of
these devices to set the bus address in order to properly communicate with the ECC-50/100 panel.
Any combination of up to eight (8) remote consoles (ECC-LOC, ECC-RPU, and ECC-RM) can be
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
Transformer (ECC-XRM-70V)
RMS
Transformer can be used to convert the integral 25 V
RMS
speakers already exist or are to be installed. Speaker wiring continues to be super-
RMS
ECC-CE6
Figure 2.43 70.7 V
RMS
operation with the optional amplifier, use model ECC-50W-70V.
RMS
DISCONNECT POWER
Transformer Installation
Installation
amplifier for installations