Installation of Option Modules
4.
Plug the supplied power cable into J10 on the main control board, then into J1 on the audio
amplifier. Plug the supplied control cable into J11 on the main control board, then into J2 on
the audio amplifier.
5.
Configure the slide switches, SW6 and SW7, per Figure 2.35. Do not use any other setting.
6.
Configure the slide switch, SW5, on the main control board for 25V or 70V operation. (70V
operation requires Amplifier model ECC-50W-70V and the ECC-XRM-70V transformer.)
7.
Connect field wiring to TB21 on the main control board (if not using the amplifier as backup).
Refer to Figure 2.15 on page 37 for illustration of speaker connections if the amplifier is being
used to expand system power to 100 watts (providing dual 50 watt speaker circuits).
8.
Configure the Audio Amplifier for primary or backup amplifier operation through the web-
based programming utility.
TB15
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
ECC-50/100
main control board
(Not populated on 70V boards) -
Figure 2.32 Installation of the Optional Audio Amplifier
ECC-MCB-PCA
Rev.
Connect J2 to J11
Connect J1 to J10
J12
LED1 - Power
SW5 - 75W
NOT USED
SW6 - 50W
SW7 - 35W - NOT USED
SW4 - Fail Test Switch
LED3 - Enabled
LED2 - Limit
LED4 - Fault
J9
RTZM
Installation
BDA
BDA
Power
Control
+-
ECC-50W-25/70V
51

Hide quick links: