Installation

2.7 ECC-LOC Local Operator Console

CAUTION:
!
THE ECC-LOC IS A SEPARATE DEVICE, NOT PART OF THE ECC-50/100 ASSEMBLY!
Wiring for the Local Operator Console is accomplished between TB24, TB12, and TB22 on the
ECC-50/100 main control board to TB3, TB4, and TB5 on the LOC. If the ECC-LOC is the last
device on the audio and data bus chain, signal terminations are required. For the external data bus,
a removable jumper must be on pins 1 and 2 of JP2 when the LOC is the last device on the chain.
If the ECC-LOC is not the last device, the jumper must be on pins 2 and 3 of JP2 as shown below.
For the external audio riser, when the LOC is the last device, termination ELR-15K must be con-
nected to pins 5 and 6 on TB5. T-taps and multiple home runs to the main control board are not
allowed for the external data bus or the external data riser.
ECC-LOC
display board
Figure 2.22 Local Operator Console Wiring (Class B/Style Y)
42
EXTERNAL WIRING CONNECTIONS
ECC-MCB-PCA
Rev.
J12
TB15
J9
RTZM
ECC-50/100
main control board
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
ECC-LOC Local Operator Console
external operator interface
+
TB24
-
external data bus
B
TB12
A
B
A
audio riser
+
TB22
-
TB2
B
A
TB3
+
-
B
A
TB4
+
-
JP2
(shown jumpered
on pins 2 and 3)
-
+
TB5
-
+
power - 24VDC
external
to next
operator
interface or
amplifier
to next operator
interface or amplifier
(or, if last device,
signal termination
ELR-15K)