Section 3: Programming - Honeywell ECC-50/100 Instruction Manual

Emergency command center, multipurpose emergency voice evacuation panels
Table of Contents

Advertisement

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, and in the standard for Communication and Control Units for
Mass Notification Systems, UL 2572, certain programming features or options must be limited to specific values or not used at all
as indicated below:
Permitted in
Program feature
UL 864/UL 2572?
or option
(Y/N)
AC Loss Delay
24 Hour Resound
Active With Page
Page Timeout
All ECC programming is done using the built-in web-based programming utility. It is recom-
mended that tone selection, message repeat cycles and background music options be reviewed and
approved by the local AHJ.
To start programming, use a standard CAT5e Ethernet cable to connect a personal computer's IP
port (Ethernet) to the IP port (Ethernet) J2 on the main control board (right side of the board). Set
the computer's local area network connection address as follows:
IP address: 169.254.3.5
Subnet mask: 255.255.0.0
NOTE: Be sure to record the computer's original addresses so they can be restored when ECC
programming is complete.
Activate the PC's web browser (Microsoft Internet Explorer version 8 or Mozilla Firefox). Enter
the following in the browser's navigation bar:
http://169.254.3.3
The main menu will display and allow further menu navigation.
NOTE: All screen shots reflect default programming.
Security and Data Protection:
NO ENCRYPTION EMPLOYED
Communication Security:
– a. Level 1
Stored Data Security:
– a. Level 0
Access Control Security:
– a. Level 1
Physical Security:
– a. Level 1
Audit Control: not provided
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016

Section 3: Programming

AND OTHER INVOLVED PARTIES
Possible settings
Y
AC Loss Delay = 0, 2 (factory default), 6, 12, or 23 hours
Refer to "AC Loss Delay" on page 62.
Y
24 Hour Resound = Enabled
24 Hour Resound = Disabled
Refer to "24 Hour Resound" on page 62
N
Enable/Disable
N
0-60 in 15 second increments
Settings permitted in
UL 864/UL 2572
AC Loss Delay = 2 hours
24 Hour Resound
Enabled
Disabled
0 seconds