Programmed Activation by FACP
example below) will be generated over speaker circuits 3 and 4. If an addressable device (address
21 in example below) programmed to Zone 32 is then activated, the highest priority message pro-
grammed to Zone 32, 35, or 36 (Message 1 in example below) will be generated over all speaker
circuits.
Addressable Pull Station
(address 09)
Addressable Pull Station
(address 21)
Addressable Pull Station
(address 15)

FACP Message Assignment - Zone Specific

The FACP can be programmed to allow a specific addressable input device to generate one of four-
teen messages over any speaker circuit. Any one of the fourteen messages can be programmed to
each of the available zones (Zone 1 through Zone 99). In the following example, assume that Zone
5 is programmed to Message 1, Zone 7 is programmed to Message 2, and Zone 35 is not pro-
grammed to a message.
Example 3: If two devices are being programmed and the first addressable input device is pro-
grammed to Zone 7 and Zone 35, and a second addressable input device is programmed to Zone 5
and Zone 35, activation of the first addressable input device (address 12 in the example below) will
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
Programmed to
Zone 35
Message 4
(lowest priority of the three)
Programmed to
Zone 32
Message 1
(highest priority of the three)
Programmed to
Zone 36
Message 3
(2nd highest priority of the three)
Speaker Circuit 1
Speaker Circuit 2
Speaker Circuit 3
activate
Speaker Circuit 4
Speaker Circuit 5
Speaker Circuit 6
Speaker Circuit 7
Speaker Circuit 8
Speaker Circuit 9
Speaker Circuit 10
Speaker Circuit 11
Speaker Circuit 12
Speaker Circuit 13
Speaker Circuit 14
Speaker Circuit 15
Speaker Circuit 16
activate
Speaker Circuit 17
Speaker Circuit 18
Speaker Circuit 19
Speaker Circuit 20
Speaker Circuit 21
Speaker Circuit 22
Speaker Circuit 23
Speaker Circuit 24
activate