Trouble Relay - Tb2; Ac Power Loss Relay - Tb3; 2: Speaker Circuits - Honeywell NOTIFIER NFC-50/100 Instruction Manual

Table of Contents

Advertisement

Output Circuits

Trouble Relay - TB2

The main control board provides a Form-C Trouble relay for independent, general system fault monitoring. This relay is 'fail safe',
meaning that it is normally energized. Should system power shut off, this relay will de-energize, transferring its contacts.

AC Power Loss Relay - TB3

The main control board provides a Form-C AC Power Loss relay.
2.6.2 Speaker Circuits
One Speaker Circuit Style Y (Class B) or Style Z (Class A) standard
Two Speaker Circuits Style Y (Class B) or Style Z (Class A) with NFC-BDA-25/70V
Four Speaker Circuits Style Z (Class B) or Style Z (Class A) or Style Y with NFC-CE6
Eight Speaker Circuits Style Z (Class B) or Style Z (Class A) or Style Y with NFC-BDA-25/70V and NFC-CE6
The integral amplifier and optional amplifier each provide audio for one Speaker Circuit. The circuit can be wired Style Y (Class B) or
Style Z (Class A). Each supervised and power-limited (Class 2) circuit is capable of 50 watts of power. Refer to the Notifier Device
Compatibility Document for a listing of compatible speakers.
CAUTION: OBSERVE POLARITY
!
MATCH PROPER POLARITY CONNECTIONS TO FIELD WIRING AND SPEAKERS. POLARITY SHOWN IS IN THE
STANDBY AND ALARM CONDITIONS.
Shielded cable is not required, however, shielded cable will reduce RFI/EMI emissions and susceptibility. For additional information,
refer to "Wiring Requirements" on page 82.
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
ELR required for
Style Y - Class B only
15K, 1 watt, P/N:ELR-15K
Shield
TB20
Figure 2.15 Speaker Circuit Connections
TB2
Shown in energized,
non trouble condition
Figure 2.13 Trouble Relay
TB3
Figure 2.14 AC Power Loss Relay
Style Z (Class A) Circuit
TB21
Shown in normal
AC Power condition
Installation
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier nfc-50/100eNotifier firstcommand seriesNotifier firstcommand nfc-50/100Notifier firstcommand nfc-50/100e