Power And Control Cables; Configuration - Honeywell ECC-50/100 Instruction Manual

Emergency command center, multipurpose emergency voice evacuation panels
Table of Contents

Advertisement

Installation
Main Control Board
ECC-MCB-PCA
Rev.
P1
TB15
J9
RTZM
Power and
Control Harness
Connections

Power and Control Cables

Control cable
Align tab with notch in
board connector.

Configuration

Enable Switches, SW6 & SW7
SW6 must be enabled. Do not enable SW7.
Switches come from the factory disabled.
Note that the board is installed upside-down.
Pay close attention when setting switches.
Figure 2.35 shows the amplifier in its installed
position, not the actual silk-screening on the
board.
FAIL TEST Switch, SW4
This switch is not used. It should always be set
to "Normal".
52
J10 J11
1. Attach four
standoffs (p/n
J12
42227) at
locations
indicated.
2. Align
amplifier over
J1
J2
standoffs.
Attach with four
screws.
3. Attach power
harnesses
(included with
Amplifier
amplifier - refer
to Figure 2.34):
• J1 on amplifier to J10 on ECC
• J2 on amplifier to J11 on ECC
Figure 2.33 ECC-50W-25/70V Installation
p/n 75690
Tab
Figure 2.34 Control and Power Cables
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
TB15
Power cable
p/n 75689
Align where
there is no pin.
Align cable connectors
over spaces and pins.
Figure 2.35 Enable Switches
Figure 2.36 FAIL TEST Switch
Installation of Option Modules
ECC-MCB-PCA
Rev.
J12
+-
J9
RTZM
SW6 is shown enabled.
Do not enable.