Appendix C: Canadian Applications

When using the ECC in Canadian Applications, note the following:
The ECC-50/100 is for fire evacuation use only.
The ECC-50DA, ECC-125DA, and ECC-50BDA amplifiers are not permitted for use in
Canada.
The ECC-RPU and ECC-RM are not permitted for use in Canada.
The ECC-50/100 must be mounted next to the FACP.
C.1 Audio Room Isolator Modules
C.1.1 Description
The audio isolator modules described below may be used to isolate short circuits during alarm sig-
naling.
AIM-1A This module provides isolation to a separate circuit on an audio riser. A short circuit on
an AIM-1A speaker circuit will not disable other speaker circuits on the riser.
RSM-1A This module works the same as the AIM-1A, with the exception that there is a silence
button for in-suite operation. The silence button will silence the audible signal to the module's cir-
cuit for ten minutes during alarm. Resounding will occur automatically after ten minutes or upon
activation of a new audio alert.
C.1.2 Panel Programming
"Canadian Configuration" and "Canadian Isolator Modules" must be enabled in ECCNFC pro-
gramming. Refer to "General/NAC Options" on page 61. In addition, "NAC Type" must be set for
steady operation. See "NAC Options" on page 63.
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
103