When using the NFC in Canadian Applications, note the following:
The NFC-50/100 is for fire evacuation use only.
The NFC-50DA, NFC-125DA, and NFC-50/100DA amplifiers are not permitted for use in Canada.
The NFC-RPU and NFC-RM are not permitted for use in Canada.
The NFC-50/100 must be mounted next to the FACP.
C.1 Audio Room Isolator Modules
C.1.1 Description
The audio isolator modules described below may be used to isolate short circuits during alarm signaling.
This module provides isolation to a separate circuit on an audio riser. A short circuit on an AIM-1A speaker circuit will not dis-
AIM-1A
able other speaker circuits on the riser.
This module works the same as the AIM-1A, with the exception that there is a silence button for in-suite operation. The silence
RSM-1A
button will silence the audible signal to the module's circuit for ten minutes during alarm. Resounding will occur automatically after ten
minutes or upon activation of a new audio alert.
C.1.2 Panel Programming
"Canadian Configuration" and "Canadian Isolator Modules" must be enabled in ECCNFC programming. Refer to "General/NAC
Options" on page 53. In addition, "NAC Type" must be set for steady operation. See "NAC Options" on page 54.
C.1.3 Applications
The following figures illustrate typical applications for audio isolator modules. Jumper settings are specified below to configure opera-
tion with speaker circuits. Jumpers are located on the back side of each module.
AIM-1A
Remove jumpers 1 & 2.
From
NFC
Speaker
Circuit
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018

Appendix C: Canadian Applications

AIM-1A
Figure C.1 Jumper Settings
AIM-1A/
RSM-1A
optional
TB19 on
NFC
NAC
(24VDC)
Supervised Speakers
Figure C.2 RSM-1A/AIM-1A Module Wiring
RSM-1A
Remove jumpers 1 & 2.
Jumper 3
to next module, ELR,
or Class A return
24V to next
device
4-wire
return
From
NFC
Speaker
Circuit
Non-supervised Speakers
RSM-1A
to next module, ELR, or Class A return
24V to
next
AIM-1A/
device
RSM-1A
TB19 on
NFC
NAC
(24VDC)