Energizing Inputs; Binary Inputs - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 18
Technical data
18.3
18.4
550

Energizing inputs

Table 463:
Energizing inputs
Description
Rated frequency
Operating range
Current inputs
Rated current, I
Thermal withstand capability:
Continuously
For 1 s
For 10 s
Dynamic current withstand:
Half-wave value
Input impedance
Voltage inputs
Rated voltage, U
Voltage withstand:
Continuous
For 10 s
Burden at rated voltage
1) Residual current
2) Phase currents or residual current

Binary inputs

Table 464:
Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption/input
Threshold voltage
Value
50/60 Hz
Rated frequency ± 5 Hz
1)
0.1/0.5 A
n
4 A
100 A
20 A
250 A
<100 mΩ
100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
n
420 V rms
450 V rms
<0.05 VA
Value
Maximum input voltage 300 V DC
24...250 V DC
1.6...1.8 mA
<0.3 W
15...221 V DC (parametrizable in the range in steps
of 1% of the rated voltage)
1MRK 502 034-UEN -
2)
1/5 A
20 A
500 A
100 A
1250 A
<20 mΩ
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents