Function Block; Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
7.2.3
7.2.4
Technical Manual
All IEC and ANSI time delayed characteristics are available.
The directional function is voltage polarized, current polarized or dual polarized.
EF4PTOC can be set directional or non-directional independently for each of the
steps.
A second harmonic blocking can be set individually for each step.

Function block

EF4PTOC
I3P*
TRIP
U3P*
TRIN1
I3PPOL*
TRIN2
BLOCK
TRIN3
BLKST1
TRIN4
BLKST2
START
BLKST3
STIN1
BLKST4
STIN2
STIN3
STIN4
STFW
STRV
2NDHARMD
IEC08000004 V1 EN
Figure 82:
EF4PTOC function block

Signals

Table 63:
EF4PTOC Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
I3PPOL
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKST1
BOOLEAN
BLKST2
BOOLEAN
BLKST3
BOOLEAN
BLKST4
BOOLEAN
Table 64:
EF4PTOC Output signals
Name
Type
TRIP
BOOLEAN
TRIN1
BOOLEAN
TRIN2
BOOLEAN
TRIN3
BOOLEAN
Table continues on next page
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for polarizing voltage
inputs
-
Three phase group signal for polarizing current
inputs
0
Block of function
0
Block of step 1 (start and trip)
0
Block of step 2 (start and trip)
0
Block of step 3 (start and trip)
0
Block of step 4 (start and trip)
Description
General trip signal
Trip signal from step 1
Trip signal from step 2
Trip signal from step 3
Section 7
Current protection
153