Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
13.15.4
Technical Manual

Signals

Table 344:
SSCBR Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK_ALM
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ALMPRES
BOOLEAN
LOPRES
BOOLEAN
SPRCHRGN
BOOLEAN
SPRCHRGD
BOOLEAN
CBCNTRST
BOOLEAN
IACCRST
BOOLEAN
SPCHTRST
BOOLEAN
TRVTRST
BOOLEAN
Table 345:
SSCBR Output signals
Name
Type
TRVTOAL
BOOLEAN
TRVTCAL
BOOLEAN
SPRCHRAL
BOOLEAN
OPRALM
BOOLEAN
OPRLOALM
BOOLEAN
IACCALM
BOOLEAN
IACCLOAL
BOOLEAN
CBLIFEAL
BOOLEAN
NOOPRALM
BOOLEAN
PRESALM
BOOLEAN
PRESLO
BOOLEAN
CBOPEN
BOOLEAN
CBINVPOS
BOOLEAN
CBCLOSED
BOOLEAN
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Block all the alarms
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Binary pressure alarm input
0
Binary pressure input for lockout indication
0
CB spring charging started input
0
CB spring charged input
0
Reset input for CB remaining life and operation
counter
0
Reset accumulated currents power
0
Reset spring charge time
0
Reset travel time
Description
CB open travel time exceeded set value
CB close travel time exceeded set value
Spring charging time has crossed the set value
Number of CB operations exceeds alarm limit
Number of CB operations exceeds lockout limit
Accumulated currents power (Iyt),exceeded alarm
limit
Accumulated currents power (Iyt),exceeded
lockout limit
Remaining life of CB exceeded alarm limit
CB 'not operated for long time' alarm
Pressure below alarm level
Pressure below lockout level
CB is in open position
CB is in intermediate position
CB is in closed position
Section 13
Monitoring
429

Advertisement

Table of Contents
loading

Table of Contents