Monitored Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 7
Current protection
Name
Characterist4
I4>
t4
k4
IMin4
t4Min
Table 60:
OC4PTOC Non group settings (basic)
Name
GlobalBaseSel
MeasType
7.1.6
148
Values (Range)
Unit
ANSI Ext. inv.
-
ANSI Very inv.
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
5 - 2500
%IB
0.000 - 60.000
s
0.05 - 999.00
-
1 - 10000
%IB
0.000 - 60.000
s
Values (Range)
Unit
1 - 6
-
DFT
-
RMS

Monitored data

Table 61:
OC4PTOC Monitored data
Name
DIRL1
DIRL2
DIRL3
IL1
IL2
IL3
Step
Default
-
ANSI Def. Time
1
175
0.001
2.000
0.01
0.05
1
17
0.001
0.000
Step
Default
1
1
-
DFT
Type
Values (Range)
INTEGER
0=No direction
1=Forward
2=Reverse
INTEGER
0=No direction
1=Forward
2=Reverse
INTEGER
0=No direction
1=Forward
2=Reverse
REAL
-
REAL
-
REAL
-
1MRK 502 034-UEN -
Description
Selection of time delay curve type for
step 4
Phase current operate level for step 4 in
% of IBase
Definite time delay of step 4
Time multiplier for the inverse time delay
for step 4
Minimum operate current for step4 in %
of IBase
Minimum operate time for inverse curves
for step 4
Description
Selection of one of the Global Base
Value groups
Selection between DFT and RMS
measurement
Unit
Description
-
Direction for phase L1
-
Direction for phase L2
-
Direction for phase L3
A
Current in phase L1
A
Current in phase L2
A
Current in phase L3
Technical Manual