Advertisement

1MRK 502 034-UEN -
11.3.5
Table 197:
SLGGIO Non group settings (basic)
Name
Values (Range)
Operation
NrPos
OutType
tPulse
tDelay
StopAtExtremes
11.3.6
11.3.7
Technical Manual
Name
P30
P31
P32
SWPOSN

Settings

Unit
Off
-
On
2 - 32
-
Pulsed
-
Steady
0.000 - 60.000
s
0.000 - 60000.000
s
Disabled
-
Enabled

Monitored data

Table 198:
SLGGIO Monitored data
Name
SWPOSN

Operation principle

The logic rotating switch for function selection and LHMI presentation (SLGGIO)
function has two operating inputs – UP and DOWN. When a signal is received on
the UP input, the block will activate the output next to the present activated output,
in ascending order (if the present activated output is 3 – for example and one
operates the UP input, then the output 4 will be activated). When a signal is
received on the DOWN input, the block will activate the output next to the present
activated output, in descending order (if the present activated output is 3 – for
example and one operates the DOWN input, then the output 2 will be activated).
Depending on the output settings the output signals can be steady or pulsed. In case
of steady signals, in case of UP or DOWN operation, the previously active output
will be deactivated. Also, depending on the settings one can have a time delay
between the UP or DOWN activation signal positive front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the
Type
Description
BOOLEAN
Selector switch position 30
BOOLEAN
Selector switch position 31
BOOLEAN
Selector switch position 32
INTEGER
Switch position as integer value
Step
Default
-
Off
1
32
-
Steady
0.001
0.200
0.010
0.000
-
Disabled
Type
Values (Range)
INTEGER
-
Section 11
Description
Operation Off/On
Number of positions in the switch
Output type, steady or pulse
Operate pulse duration
Output time delay
Stop when min or max position is reached
Unit
Description
-
Switch position as
integer value
Control
301