Technical Manual
Technical data
Table 348:
SSCBR Technical data
Function
Alarm levels for open and close
travel time
Alarm levels for number of
operations
Setting of alarm for spring
charging time
Time delay for gas pressure
alarm
Time delay for gas pressure
lockout
Measurands for IEC 60870-5-103 I103MEAS
Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The measurand reporting interval set for MMXU function blocks, using the
xDbRepInt and xAngDbRepInt settings, must be coordinated with the event
reporting interval set for the IEC 60870-5-103 communication using setting
CycMeasRepTime.
Range or value
(0-200) ms
(0 - 9999)
(0.00-60.00) s
(0.00-60.00) s
(0.00-60.00) s
Section 13
Monitoring
Accuracy
± 0.5% ± 25 ms
-
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms
441