Function Block; Signals; Settings; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
15.6.3
15.6.4
15.6.5
Table 390:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Operation
15.6.6
Technical Manual

Function block

GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
IEC10000250-1-en.vsd
IEC10000250 V1 EN
Figure 233:
GOOSEINTRCV function block

Signals

Table 388:
GOOSEINTRCV Input signals
Name
BLOCK
Table 389:
GOOSEINTRCV Output signals
Name
INTOUT
DATAVALID
COMMVALID
TEST

Settings

Unit
Off
-
On

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be crossed in the SMT to
receive the integer values.
TEST
Type
Default
Description
BOOLEAN
0
Block of function
Type
Description
INTEGER
Integer output
BOOLEAN
Data valid for integer output
BOOLEAN
Communication valid for integer output
BOOLEAN
Test output
Step
Default
-
Off
Section 15
Station communication
Description
Operation Off/On
473