Signals; Settings; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 12
Logic
12.1.4
12.1.5
Table 226:
SMPPTRC Group settings (basic)
Name
Operation
tTripMin
Table 227:
SMPPTRC Group settings (advanced)
Name
TripLockout
AutoLock
12.1.6
318

Signals

Table 224:
SMPPTRC Input signals
Name
BLOCK
TRIN
SETLKOUT
RSTLKOUT
Table 225:
SMPPTRC Output signals
Name
TRIP
CLLKOUT

Settings

Values (Range)
Unit
Off
-
On
0.000 - 60.000
s
Values (Range)
Unit
Off
-
On
Off
-
On

Operation principle

The duration of a trip output signal from tripping logic SMPPTRC is settable
(tTripMin). The pulse length should be long enough to secure the breaker opening.
For three-phase tripping, SMPPTRC has a single input (TRIN) through which all
trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a
single trip output (TRIP) for connection to one or more of the IEDs binary outputs,
as well as to other functions within the IED requiring this signal.
Type
Default
Description
BOOLEAN
0
Block of function
BOOLEAN
0
Trip all phases
BOOLEAN
0
Input for setting the circuit breaker lockout function
BOOLEAN
0
Input for resetting the circuit breaker lockout
function
Type
Description
BOOLEAN
General trip signal
BOOLEAN
Circuit breaker lockout output (set until reset)
Step
Default
-
On
0.001
0.150
Step
Default
-
Off
-
Off
1MRK 502 034-UEN -
Description
Operation Off / On
Minimum duration of trip output signal
Description
On: Activate output (CLLKOUT) and trip
latch, Off: Only output
On: Lockout from input (SETLKOUT)
and trip, Off: Only input
Technical Manual