Monitored Data; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
13.15.6
13.15.7
Technical Manual

Monitored data

Table 347:
SSCBR Monitored data
Name
Type
CBOTRVT
REAL
CBCLTRVT
REAL
SPRCHRT
REAL
NO_OPR
INTEGER
NOOPRDAY
INTEGER
CBLIFEL1
INTEGER
CBLIFEL2
INTEGER
CBLIFEL3
INTEGER
IACCL1
REAL
IACCL2
REAL
IACCL3
REAL

Operation principle

The circuit breaker condition monitoring function includes different metering and
monitoring subfunctions. The functions can be enabled and disabled with the
Operation setting. The corresponding parameter values are "On" and "Off". The
operation counters are cleared when Operation is set to "Off".
The operation of the functions can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Values (Range)
Unit
-
ms
-
ms
-
s
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Section 13
Monitoring
Description
Travel time of the CB
during opening operation
Travel time of the CB
during closing operation
The charging time of the
CB spring
Number of CB operation
cycle
The number of days CB
has been inactive
CB Remaining life phase
L1
CB Remaining life phase
L2
CB Remaining life phase
L3
Accumulated currents
power (Iyt), phase L1
Accumulated currents
power (Iyt), phase L2
Accumulated currents
power (Iyt), phase L3
431

Advertisement

Table of Contents
loading