One undervoltage step with definite time characteristic is also available with the
function in order to provide funcionality for overcurrent protection with
undervoltage seal-in.

Function block

VR2PVOC
I3P*
TRIP
U3P*
TROC
BLOCK
TRUV
BLKOC
START
BLKUV
STOC
STUV
IMAX
UUMIN
IEC10000118-1-en.vsd
IEC10000118 V1 EN
Figure 109:
VR2PVOC function block

Signals

Table 119:
VR2PVOC Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKOC
BOOLEAN
BLKUV
BOOLEAN
Table 120:
VR2PVOC Output signals
Name
Type
TRIP
BOOLEAN
TROC
BOOLEAN
TRUV
BOOLEAN
START
BOOLEAN
STOC
BOOLEAN
STUV
BOOLEAN
IMAX
REAL
UUMIN
REAL
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function both stages
0
Block of voltage restraint overcurrent stage (ANSI
51V)
0
Block of under voltage function
Description
General trip signal
Trip signal from voltage restraint overcurrent stage
Trip signal from undervoltage function
General start signal
Start signal from voltage restraint overcurrent
stage
Start signal from undervoltage function
Maximum phase current magnitude
Minimum ph-to-ph voltage magnitude
Section 7
Current protection
211