Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 7
Current protection
7.2.5
Table 65:
EF4PTOC Group settings (basic)
Name
Operation
AngleRCA
polMethod
UPolMin
IPolMin
RNPol
XNPol
IN>Dir
2ndHarmStab
DirMode1
Table continues on next page
154
Name
TRIN4
START
STIN1
STIN2
STIN3
STIN4
STFW
STRV
2NDHARMD

Settings

Values (Range)
Unit
Off
-
On
-180 - 180
Deg
Voltage
-
Current
Dual
1 - 100
%UB
2 - 100
%IB
0.50 - 1000.00
ohm
0.50 - 3000.00
ohm
1 - 100
%IB
5 - 100
%
Off
-
Non-directional
Forward
Reverse
Type
Description
BOOLEAN
Trip signal from step 4
BOOLEAN
General start signal
BOOLEAN
Start signal step 1
BOOLEAN
Start signal step 2
BOOLEAN
Start signal step 3
BOOLEAN
Start signal step 4
BOOLEAN
Forward directional start signal
BOOLEAN
Reverse directional start signal
BOOLEAN
2nd harmonic block signal
Step
Default
-
Off
1
65
-
Voltage
1
1
1
5
0.01
5.00
0.01
40.00
1
10
1
20
-
Non-directional
1MRK 502 034-UEN -
Description
Operation Off / On
Relay characteristic angle (RCA)
Type of polarization
Minimum voltage level for polarization in
% of UBase
Minimum current level for polarization in
% of IBase
Real part of source Z to be used for
current polarisation
Imaginary part of source Z to be used for
current polarisation
Residual current level for direction
release in % of IBase
Second harmonic restrain operation in %
of IN amplitude
Directional mode of step 1 (off, non-
directional, forward, reverse)
Technical Manual