en | Settings
On-board Zone Response Time:
Each on-board zone response time is:
Zone status trigger time >= 400ms, must response
Zone status trigger time < 300ms, no response
On-board Zone EOL
1.
Loop Resistance (ohm)
Min
0
1650
2970
The detectors (sensors) will be connected between zone and COM terminal through EOL
series (open triggered) or parallel connection (short triggered).
The detectors (sensors) will be connected between zone and COM terminal through EOL
series connection (open triggered) or EOL parallel connection (short triggered).
The panel sets the short / open as activate when connecting with single EOL.
The valid zone number is 1-8 for AMAX 2100 / 3000, 1-16 for AMAX 4000
1.
Loop resistance (ohm)
Min
o
1650
2970
5220
Using one 2.2 Kilo resistor as EOL of the tamper zone, which works together with the zone
EOL 2.2 Kilo.
2014.4 | 01 | F.01U.267.112
Single EOL: If the zone tamper function is not selected, each zone uses a single 2.2 Kilo
ohm EOL. The panel can detect the zone as short, normal or open.
Type
2200
COM
Zone
COM
Zone
Dual EOL: If the tamper supervision is set, we only can use the NC contact point. The EOL
status is:
Type
2200
4400
Max
1430
2750
Max
1430
2750
4950
Installation Guide
AMAX panel 4000 / AMAX panel 4000
Zone Status
triggered
normal
triggered
Zone Status
tamper
normal
triggered
tamper
Bosch Sicherheitssysteme GmbH
EN