en | Troubleshooting
All keyfob configuration are correct and fault is reset.
Supervise:
1.
2.
2 - Power Failure
The zone indicator 2 lights to indicate power faults. Enter [2] to step to power faults list for
more information.
Condition:
1.
2.
3.
Restore:
1.
2.
3.
4.
5.
6.
Condition:
1.
2.
Restore:
When Battery voltage rises to 12V+-1%, Dynamic Battery test is performed (time set in
Programming address 204), and fault is reset.
Supervise:
1.
2.
3.
4.
Condition:
Aux Power Supply Voltage is lower than 9V.
Restore:
Voltage is raised to 12 and fault is reset.
Supervise:
1.
2.
3.
2014.4 | 01 | F.01U.267.112
Slow flash FAULT indicator (refer to Keypad Indicators for the detailed description).
When the fault is reset, the FAULT indicator is turned off when there is no other system
fault.
Panel AC Failure
AC supply deficiency to panel caused by transformer.
Power supply fuse broken (230V).
Power supply disconnected (230V).
AC MAINS supply is reconnected and fault is reset.
Monitor the voltage by MPU.
f the AC fault is not restored in 1 hour after the fault occurred, report the fault to
configured destination on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators for the detailed description).
As the AC supply is reconnected, the MAINS indicator is back to light (except in
Programming Mode or Code Functions Mode).
When the fault is reset, send the restored report to the configured destinations.
Battery Low Battery
Battery voltage is lower than 11V+-1%.
No battery connected.
The system performs a Dynamic Battery Test every time (set in address 204) and every
time the system is armed or reset.
Report the low battery to the configured destination programmed on address 124.
Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
Panel Aux Power Failure
Monitor the voltage by MPU.
Report the AUX power fault to the configured destination programmed on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators for the detailed description).