AMAX panel 4000 / AMAX panel 4000
EN
4.
Condition:
Bosch option bus power supply Voltage is lower than 9V+-5%.
Restore:
Voltage is raised to 12V and fault is reset.
Supervise:
1.
2.
3.
4.
Condition:
There is an AC power failure to the repeater, or the repeater is not wired correctly, if wireless
module is enabled.
Restore:
The repeater AC power restored and fault is reset.
Supervise:
1.
2.
3.
Condition:
The repeater has experienced a low battery condition, if wireless module is enabled.
Restore:
The battery restored and fault is reset.
Supervise:
1.
2.
3.
Condition:
The sensor has experienced a low battery condition, if wireless module is enabled.
Restore:
The sensor battery restored and fault is reset.
Supervise:
1.
2.
3.
Bosch Sicherheitssysteme GmbH
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
Bosch Option Bus Power Failure
Monitor the voltage by MPU.
Report the Bosch Option Bus Power Supply fault to the configured destination
programmed on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators for the detailed description).
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
RF Repeater AC Power Failure
Report the repeater AC power fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators for the detailed description).
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
RF Repeater Battery Failure
Report the repeater battery fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators for the detailed description).
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
RF Sensor Power Failure
Report the sensor power fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators for the detailed description).
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
Installation Guide
Troubleshooting | en
145