4 Individual remote controls
PC-ARF
Indi-
Items Optional Function
vidual
setting
Room temperature
d6
control for energy
saving
Fall distance of
elevating panel
d7
(Indoor units with
the elevating grille
function only)
KPI: Ventilation
mode (*3)
E1
Econofresh:
cooling mode (*3)
KPI: Increased air
supply volume (*3)
E2
Econofresh:
enthalpy sensor
(*3)
E3
Not used
Pre-cooling / Pre-
E4
heating period (*3)
E5
Not prepared
×
Indoor fan
operation time after
E6
cooling operation
stoppage
E7
Not prepared
Fan operation
E8
control at heating
Thermo-OFF
E9
Not prepared
-
EA
Not prepared
-
Fan operation
Eb
control at cooling
Thermo-OFF
Forced Thermo-
EC
ON stoppage at
cooling
71
TCGB0106 rev.0 - 12/2014
Setting
Contents
condition
00
Not available
01
Available
Not used (Use as 00
00~07
conditions)
00
Automatic ventilation
Ventilation by total heat
01
exchanger
Ventilation with bypass
02
(no total heat
exchanger)
00
Not available
Outdoor cooling mode
01/02
(all-fresh)
00
Not available
01
Available
00
Not available
01
Available
00
Not Used
Used as setting for
01
conditions 00
KPI:
00
Standard
01
30 minutes
02
60 minutes
Econofresh kit:
00
Standard
01/02
CO
sensor
2
Not used
00
(Use as 00 conditions)
01
00
Not available
01
60 min.
02
120 min.
00
Not used
(Use as 00 conditions)
01
00
Not available
01
SLOW
Not used
00
01
(Use as 00 conditions)
Not used
00
01
(Use as 00 conditions)
00
Not available
01
LOW
02
SLOW
00
Not available
01
Available
Indi-
Items Optional Function
vidual
setting
Ed
Not prepared
-
Automatic fan
EE
speed control
F0
Not prepared
-
Automatic OFF
timer setting
* Do not set the
functions "0C"~"0F"
F1
×
when 2 (two)
remote control
switches are used
in the same remote
control group.
Remote control
F2
main-sub setting
×
(*10)
Automatic reset of
F3
setting temperature
×
(*4)
Automatic reset
F4
×
time
Automatic reset
F5
temperature for
×
cooling (*5)
Automatic reset
F6
temperature for
×
heating (*6)
Operation
stoppage
prevention by
F7
×
remote control
switch operational
error (*7)
Setting
Contents
condition
Not used
00
01
(Use as 00 conditions)
00
Not available
01
Available
-
Not used
00
No function
01
OFF Timer by 1 hr
02
OFF Timer by 2 hrs
...
...
23
OFF Timer by 23 hrs
24
OFF Timer by 24 hrs
0A
OFF Timer by 30 min
0B
OFF Timer by 90 min
0C
OFF Timer by 40 min
0D
OFF Timer by 45 min
0E
OFF Timer by 50 min
0F
OFF Timer by 55 min
00
Main
01
Sub
00
Not available
01
Available
00
30 min. (Factory setting)
01
15 min.
02
60 min.
03
90 min.
19
19
C
o
20
20
C
o
...
...
25
25
C (Factory setting)
o
...
...
29
29
C
o
30
30
C
o
17
17
C
o
18
18
C
o
...
...
21
21
C (Factory setting)
o
...
...
29
29
C
o
30
30
C
o
00
Not available
01
Available
4