8 Control support devices
PSC-6RAD

8.2.3.3 Connection with room air-conditioner.

1 Remove the front cover of room air-conditioner and the cover of electrical box.
2 The cable attached with the connector of RAC adapter shall be connected with the connector of indoor PCB.
3 Install the electrical box cover paying attention not to clamp the cable. See an installation manual of each room air-
conditioner for confirming how to connect and how to assemble the cable of RAC adapter.
C A U T I O N
Disconnect the power plug before performing this work.
Turn OFF a breaker power source in case that the power comes from outdoor unit.

8.2.3.4 Connection of transmission cable

H-LINK transmission cable connecting to RAC adapter shall be connected to H-LINK.
RAC adpater H-LINK
wiring
C A U T I O N
Incorrect wiring may cause a failure of RAC adapter. Especially pay attention not to
apply the high voltage like AC400/230V.
Do not perform the wiring work with power of the central station or RAC adapter being
supplied. It may cause the malfunction. Turn OFF devices when performing the wiring
work.
The RAC adapter side cable should not overload to the connector.
Do not clamp the cable when attaching the RAC adapter cover.
Band should be in the fixed position.
714
TCGB0106 rev.0 - 12/2014
Use enclosed connector
Connector (accessory)
To other connection
device of H-LINK
Band
Fixed
position