6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)

Operation panel
The Operation Panel has the following access fields offering complete control of the units:
Setting
Timer
Unit configuration
System Status
Auto Cool/Heat
Cold Draft
Power meter
Each of these fields is explained below.
N O T E
Visibility of these fields depends on privilege level of the user.
Setting
This option shows the parameters which can be selected for each indoor unit.
1
2
3
After selecting the parameters to be adjusted, press Update to send the order to the units selected or Cancel to cancel
the operation.
1 Select the unit. The unit selected in the table of indoor units is identified by the Location field. Using the Set by field,
select the group of units whose parameters you want to adjust:
-
Unit: The unit selected.
Outdoor: All the indoor units which belong to the same cooling circuit.
-
Area: All the units which are in the same area.
-
-
All units: All the units controlled by CSNET WEB.
2 Adjust parameters. Click with the mouse on the parameter you want to select. Select the temperature with the buttons
"" or ">". The temperature margin is:
-
From 19ºC to 30ºC for cooling.
-
From 17ºC to 30ºC for heating.
Select the fan speed and the position of the baffle plate by pushing the Fan speed and Louver buttons.
N O T E
Automatic mode cannot be set for units with the RAC adapter PSC-6RAD so that the option will not appear on screen when this type of
units is selected.
3 Parameter lock. The parameters selected in RCS Lock will remain locked in the previous position when the option was
activated. This means that they cannot be modified from the remote control.
N O T E
ON/Off lock only locks in OFF. Unit always can be stopped from the remote control.
462
462
TCGB0106 rev.0 - 12/2014