Technical specifications
16.2 Electromagnetic compatibility
Pulse-shaped disturbances
The table below shows the electromagnetic compatibility of the S7-1500R/H redundant
system with regard to pulse-shaped disturbances.
Table 16- 1
Pulse-shaped disturbance
Electrostatic discharge in accordance
with IEC 61000-4-2.
Burst pulses (high-speed transient dis-
turbances) in accordance with
IEC 61000-4-4.
High-energy single pulse (surge) in accordance with IEC 61000-4-5
External protective wiring required (not for 230 V modules)
You can find more information in the Designing interference-free controllers Func-
tion Manual.
Sinusoidal disturbances
The following table shows the electromagnetic compatibility of the S7-1500R/H redundant
system with respect to sinusoidal disturbances (RF radiation).
Table 16- 2
RF radiation in accordance with IEC 61000-4-3/NAMUR 21
Electromagnetic RF field, amplitude-modulated
80 MHz to 2.7 GHz
2.7 GHz to 6 GHz
80 % AM (1 kHz)
488
Pulse-shaped disturbances
Asymmetric coupling
Symmetric coupling
Sinusoidal disturbances with RF radiation
Test voltage
Air discharge: ±8 kV
Contact discharge: ±6 kV
±2 kV (power supply line)
±2 kV (signal cable > 30 m)
±1 kV (signal cable < 30 m)
±2 kV (power supply cables)
DC with protective elements
±2 kV (signal/data line only > 30 m), with
protective elements
±1 kV (power supply cable) DC with pro-
tective elements
±1 kV (signal/data line only > 30 m), with
protective elements
10 V/m
3 V/m
System Manual, 01/2024, A5E41814787-AF
Corresponds
with degree of
severity
3
3
3
4
3
3
Corresponds with de-
gree of severity
3
2
S7-1500R/H redundant system