Connecting Redundancy Connections (Fiber-Optic Cables); Synchronization Modules For S7-1500H; Selecting Fiber-Optic Cables - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Wiring
8.9 Connecting interfaces for communication with S7-1500H
8.9.1

Connecting redundancy connections (fiber-optic cables)

8.9.1.1

Synchronization modules for S7-1500H

Introduction
You use the synchronization modules to create two redundancy connections between the
two H-CPUs. You need two identical synchronization modules per CPU which you connect
with fiber-optic cables.
View
Figure 8-8
Maximum cable length (fiber-optic cable) between the two H-CPUs
In the S7-1500H redundant system, you need to use four synchronization modules of the
same type. You can order the following types of synchronization modules:
Maximum cable lengths between the two H-
CPUs
10 m
10 km (minimum length: 2 m)
40 km (minimum length: 8 km)
8.9.1.2

Selecting fiber-optic cables

Introduction
You can find an overview of fiber-optic cables, the necessary conditions and technical
specifications in the system manual Industrial Ethernet/PROFINET Passive network
components (https://support.industry.siemens.com/cs/ww/en/view/84922825).
274
Synchronization module
Article number
6ES7960-1CB00-0AA5
6ES7960-1FB00-0AA5
6ES7960-1FE00-0AA5
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500r/h

Table of Contents