Failure Of The Communications Processor At The Primary Cpu With Failure Of The Backup Cpu - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Application planning
6.5 Failure scenarios
Diagnostics
System state, operating states and error displays after the failure of both PROFINET cables:
• Redundant system → RUN-Redundant system state
• Primary CPU/Backup CPU → RUN-Redundant operating state
– MAINT LED → yellow light: No backup AR.
– ERROR LED → flashes red: One or more IO devices have failed.
Note
To get detailed diagnostics information, evaluate the diagnostics buffer.
Solution
Replace the defective PROFINET cables. You can find additional information on the procedure
in the section Replacing defective PROFINET cables.
6.5.4.8
Failure of the communications processor at the primary CPU with failure of the
backup CPU
Introduction
The following redundancy scenario describes the effects of a defective CP 1543-1
communications processor at the primary CPU with failure of the backup CPU.