Connecting The Supply Voltage - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Wiring

8.5 Connecting the supply voltage

Permissible cable temperature
Note
Permissible cable temperature
When selecting the cable, note that the cable temperature during operation can be up to
30 °C higher than the ambient temperature of the S7-1500R/H redundant system.
Example: If you use the system in a switchgear cabinet at an ambient temperature of 30 °C,
you must use a connecting conductor with a temperature range of at least 60 °C.
With terminals that carry a current load of ≥ 8 A during operation, you must expect a cable
temperature of up to 65 °C above the ambient temperature.
You can more exactly determine the required cable temperature for each application. To do
so, measure the cable temperature in the system at a load corresponding to the maximum
possible power and ambient temperature values.
You should specify other connection types and material requirements based on the electrical
characteristics of the circuits you use and the installation environment.
8.5
Connecting the supply voltage
Introduction
The supply voltage is supplied over a 4-pin connector at the front of or bottom of the R/H-
CPU.
Connection for supply voltage (X80)
The connections of the 4-pole connector have the following meaning:
Figure 8-3
The cable connector enables you to loop the supply voltage uninterrupted, even when it is
unplugged.
266
+24 V DC of the supply voltage (current limited to 10 A)
Ground of the supply voltage (current limited to 10 A)
Ground of the supply voltage for loop-through
+24 V DC of the supply voltage for loop-through
Spring opener (one spring opener per terminal)
Connection for supply voltage
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500r/h

Table of Contents