Failure Of The Primary Cpu When Io Devices Have Failed In The Profinet Ring - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Application planning
6.5 Failure scenarios
Diagnostics
System state and operating states after cable interruptions:
• Redundant system → System state defective (undefined: Each R-CPU is in the RUN-Solo
system state).
• Primary CPU → RUN operating state
– MAINT LED → yellow light: The R-system is not in the RUN-Redundant system state. No
– ERROR LED → flashes red: An IO device has failed.
• Primary CPU (previously backup CPU) → RUN operating state
– MAINT LED → yellow light: The R-system is not in the RUN-Redundant system state. No
– ERROR LED → flashes red: An IO device has failed.
Note
To get detailed diagnostics information, evaluate the diagnostics buffer.
Solution
Please note the following solution:
Note
Before you replace the defective PROFINET cables, you must switch both R-CPUs to the STOP
operating state. Only then repair the PROFINET cables in the PROFINET ring. Afterwards,
switch the R-CPUs back to the RUN operating state.
You can find additional information on the procedure in the section Replacing defective
redundancy connections (Page 447).
6.5.3.3

Failure of the primary CPU when IO devices have failed in the PROFINET ring

Introduction
The following failure scenario describes the effects of a defective IO device in the PROFINET
ring and a defective primary CPU.
206
partner CPU has been found in the R-system. The PROFINET ring is open.
partner CPU has been found in the R-system. The PROFINET ring is open.
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF